We develop software for structural engineers and detailers. Our development team researches, tests, and applies new methods of analyzing the behaviour of structures and their members. Based on this, we created IDEA StatiCa โ€“ software that enables engineers to work faster, evaluate requirements of the national code thoroughly, and use the optimal amount of material. For us, creating software is a way to contribute to making every new construction around the world safer and cheaper.

Idea StatiCa Resellers

Methods and regulations – Fire resistance checks

IDEA StatiCa - Fire resistance checks
Fire resistance is the ability of a building structure to resist the effects of a fully developed fire without losing its load-bearing capacity, stability, integrity, and insulation. What limit states do we have to deal with, and how should a structural engineer properly assess the effects of fire?

Fire resistance limit states

The limit state of fire resistance is based primarily on the type of construction. Whether it is a load-bearing or non-load-bearing element, or whether it is a wall, column or door. The regulations define a number of limit states. The four most commonly used types are R, E, I, W.

IDEA StatiCa - Limit States

(a) R = Resistance and stability, (b) E = Integrity, (c) I = Insulating function, (d) W = Firewalls

Limit state โ€žRโ€œ (resistance and stability)

The limit state ‘R’ applies to all load-bearing structures (including those inside the fire compartment). Especially those that ensure the building stability. Those must persist in their load-bearing function even during a fire. For limit state ‘R’, it does not matter if the structure is a beam or plate type. The R limit state must be fulfilled for walls, columns, beams, roof trusses, purlins, but also by stiffeners, etc.

Limit stateย โ€žEโ€œย (integrity)

Limit state ‘E’ applies to all surface of fire separation structures. During a fire, a crack is not allowed to be formed in the fire compartmentation structure through which flames could pass or through which hot gases could penetrate into another compartment. Fire integrity shall be met by firewalls and ceilings separating the fire compartments, other fire partitions or soffits (behind which may be process ducts, etc.), and fire closures (e.g. doors), where appropriate.

Limit stateย โ€žIโ€œ (Insulating function)

Limit state ‘I’ is valid for surface fire separation structures, which are intended to prevent excessive heating of the space on the side facing away from the fire. Material on or adjacent to the unheated side shall not ignite. The insulating capacity shall be fulfilled in particular by solidly built-in flat structures such as firewalls and ceilings between fire compartments. This means that these are predominantly internal elements where fire can occur on both sides of the structure and where people on the unheated side are likely to be at risk. Fire stops opening onto a protected means of escape must also comply with Limit State ‘I’.

Limit state “W” (limitation of heat radiation)

The heat radiation restrainings apply to surface fire separation structures, it is similar to the “I”, but with less stringent requirements. Limit state ‘W’ is not capable of preventing temperature rise, it only limits to some extent the heat flux radiating from the side of the structure facing away from the fire.ย However, this radiant heat flux shall not cause the spread of the fire or endanger persons escaping in the vicinity of such a structure. It is therefore limited to 15 kW/m2.

Time of fire resistance

The fire resistance period is defined as the period of time during which the structure must resist the effects of fire or fulfill the required limit state (or more limit states). The fire resistance period is determined in minutes. The basic classification periods are set atย 15, 30, 45, 60, 90, 120, and 180 minutes.

Load during a fire resistance

According to the Eurocode, you can simplistically consider the extreme load during a fire as ย 70% of the load combination for ULS.

IDEA StatiCa - Load during a fire resistance

Fire resistance methods

The design methods vary according to the approach, accuracy, and complexity of the calculation. When analyzing a critical element, we can use theย Tabulated method, which is the most conservative one.

IDEA StatiCa - Fire resistance tabulated method

If the code-check is not satisfactory, there is the possibility to proceed to more precise methods such as theย Isotherm 500ย or the so-calledย Zone Method. In the case of an analysis of a part of the structure or even the whole structure, numerical simulations such asย conduction,ย convectionย orย radiationย can be used.ย 

Basic assumptions of the Tabulated method

  • Primarily all values are for siliceous aggregates (most susceptible to the effects of fire)
  • For limestone aggregate, the smallest required stone dimension can be reduced by 10%
  • The humidity of concrete must be less than 3%, otherwise, there is a risk of explosive spalling
  • The critical temperature of concrete reinforcement is 500 ยฐC
  • The critical temperature for prestressing reinforcement is 400 ยฐC (bars) or 350 ยฐC (tendons and wires)ย 
  • The axial distance of the reinforcement from the surface must be less than 70 mm, otherwise, surface reinforcement must be considered
  • In the case of multiple layers of reinforcement, the average axial distance from the edge shall be calculated, with the smallest axial distance of any layer fulfill at least criterion R30
  • It is possible to interpolate linearly between the values in the tables
  • The values given in the tables are minimal values and the design principles according to Eurocode must also be observed
Columnsย 

Columns are generally code-checked usingย method Aย orย B. The decision of which method to use is solely dependent on engineering choice. The code-check is valid for columns that are mainly subjected to the normal pressure and for stiffened structures.

Method A
  • The maximum effective length reaches 3 m.
  • Effective length is equal to 0.7*L for the top floor and 0.5*L for each additional floor.
  • Initial imperfections are less than 15% of the cross-section height.
  • The maximum area of reinforcement is less than 4% of the concrete cross-sectional area.
IDEA StatiCa - Fire resistance Method A
Method B
  • The method is valid only for stiffened structures.ย 
  • The effective length of the column can be more than 3 meters.
IDEA StatiCa - Fire resistance Method B
Beams

The code-check of beam elements is only possible for rectangular, T-section, or I-section cross-sections. In the next step, it is necessary to distinguish between single span or continuous beams.

IDEA StatiCa - Beams
Plates

As with beam elements, you must choose between a simply supported plate or a continuous plate. Another aspect distinguishes between supports created by walls or columns.

IDEA StatiCa - Plates

a) One-way slab, b) Two-way slab, c) Continues plate – walls, d) Continues plate – columns

Walls
  • The ratio between height to thickness must be lower than 40
  • Fire resistance EI โ€“ integrity and insulating function, bearingless
  • Fire resistance REI โ€“ integrity and insulating function, bearing function
IDEA StatiCa - Fire resistance - Walls

Summary

For code-checking the fire resistance of structures, theย Tabulated methodย is mostly preferred, according to which the engineer gets a pass/fail status very quickly. More advanced methods such as theย Isotherm 500ย orย Zone Methodย are also frequently used methods. The advanced methods are used when critical elements such as a column, beam, wall or slab fail in the tabulated method. Numerical simulation methods like conduction, convection or radiation are mainly applied in academic settings.ย IDEA StatiCa RCSย contains the aforementionedย Tabuled methods. The development at IDEA StatiCa moves the analysis fromย Tabuled methodsย to the level of numerical methods. Thus, you can look forward to non-stationary heat conduction analysis inย IDEA StatiCa Memberย in the near future.